Differential Pressure Transmitters (Model JTD9_ _ _) can measure flow rate, pressure, and fluid levels of gases, liquids, and steam, as well as transmitting 4–20 mA DC analog signals in proportion to the measured pressure.
By means of two-way communication between Model JTD9_ _ _ and a Model CFS100 or HART® communicator, operations such as self-diagnosis, range resetting, and zero adjustment can be easily accomplished.
The wide rangeability of Differential Pressure Transmitters (Model JTD920S: 0.5 to 100 kPa = a rangeability of 1:200) allows measurement over an extremely wide range and reduces the need for measurement equipment.
Other models measure minute pressure differences as low as 0.1 kPa, or withstand pressures as high as 42 MPa.
Differential Pressure Transmitter
Model | JTD910_ | JTD920_ | JTD930_ | JTD960_ |
---|---|---|---|---|
Measurement span | 0.1 to 2 kPa | 0.5 to 100 kPa | 35 to 700 kPa | 0.25 to 14 MPa |
Setting range | -1 to 1 kPa | -100 to 100 kPa | -100 to 700 kPa | -0.1 to 14 MPa |
Reference accuracy (Varies by material and measurement span) | ±0.3% | ±0.1%(Option ±0.04%) | ±0.1% | ±0.1% |
Fill fluid | Silicone oil (general purpose models), fluorine oil (oxygen and chlorine models) | |||
Waterproof and dust-proof construction | IEC IP66/IP67 | |||
Explosion-proof construction | TIIS explosion proof (Exd IICT4) | |||
Wetted material | SUS316 (diaphragm SUS316L) | SUS316 (diaphragm SUS316L), Alloy C-276, Tantalum | ||
Power | 17.9 to 45 V DC | |||
Output signal | 4 to 20 mA DC (SFN communication) 4 to 20 mA DC (HART® communication) | |||
Process connections | Rc 1/2 or 1/2 NPT internal thread |
High-Pressure Resistant Differential Pressure Transmitter
Model | JTD921_ | JTD931_ | JTD961_ | |
---|---|---|---|---|
Measurement span | 0.5 to 100 kPa | 35 to 700 kPa | 0.25 to 14 MPa | |
Setting range | -100 to 100 kPa | -100 to 700 kPa | -0.1 to 14 MPa | |
Reference accuracy (Varies by material and measurement span) | ±0.1% | ±0.1% | ±0.1% | |
Fill fluid | Silicone oil (general purpose models), fluorine oil (oxygen and chlorine models) | |||
Waterproof and dust-proof construction | IEC IP66/IP67 | |||
Explosion-proof construction | TIIS explosion proof (Exd IICT4) | |||
Wetted material | SUS316 (diaphragm SUS316L) | |||
Power | 17.9 to 45 V DC | |||
Output signal | 4 to 20 mA DC (SFN communication) 4 to 20 mA DC (HART® communication) | |||
Process connections | Rc 1/2 or 1/2 NPT internal thread |