
This is a microprocessor-based smart transmitter with excellent stability. It can be mounted on a flange on the side of a tank to measure the liquid level, interface level or specific gravity in the tank.
- Safe instrumentation: IEC 61508-compliant and SIL2-certified
- Excellent usability: zero/span adjustment without opening the cover
- Various functions: send alarm information by contact output (optional)
Advanced Transmitter Flange-Mounted Differential Pressure Transmitters (Model GTX_ _F) can be attached to a tank-side flange to measure fluid level, specific gravity, etc. We offer an extensive lineup ranging from 40 mm small bore models to 100 mm protruding flange models.
Model | GTX35F | GTX60F |
---|---|---|
Measurement span | 2.5~100 kPa | 35~3500 kPa |
Setting range | -100~100 kPa | -100~3500 kPa |
Reference accuracy(Varies by material and measurement span) | ±0.2% | ±0.15% |
Fill fluid | Silicone oil (general purpose models), fluorine oil (oxygen and chlorine models) | |
Waterproof and dust-proof construction | IEC IP66/IP67 | |
Explosion-proof construction | TIIS flameproof (Exd IICT4) KOSHA flameproof FM explosion proof, intrinsic safe and Nonincendive ATEX/NEPSI/IECEx flameproof, intrinsic safe and Type n | |
Range of operating temperatures for liquid part(Varies with pressure) | Silicone oil: -40 to 110°C Fluorine oil: -20 to 75°C | |
Range of operating pressures for liquid part(Varies with temperature) | Silicone oil: from 2 kPa abs Fluorine oil: from 54 kPa abs | |
Wetted material | SUS316 (diaphragm SUS316L), Alloy C-276, Tantalum | |
Power | 17.9~42V DC | |
Output signal | 4 to 20 mA DC (SFN communication) 4 to 20 mA DC (HART® communication) | |
Flange bore | Flush models: 80 mm, 50 mm, 40 mm. Protruding models: 100 mm, 80 mm, 50 mm | |
Safety certification | Safety Integrity Level (SIL) 2 certification |