Differential Pressure Transmitter / Pressure Transmitters Advanced Transmitter Model JT_9_ _S/W

Remote-sealed Gauge Pressure Transmitters Model JTH9_ _ _

Model No.
JTH920S, JTH920W, JTH940S, JTH940W, JTH960S, JTH960W, JTH980S, JTH980W
JTH-L

Remote-sealed Gauge Pressure Transmitters (Model JTH9_ _ _) are used to measure pressure (pressure, fluid level, etc.) of very hot as well as highly corrosive and condensable fluids. We offer an extensive lineup including small bore flange models starting at 40A and models for high temperature (including high temperature high vacuum) applications.

ModelJTH920_JTH940_JTH960_JTH980_
Measuring span2.5 to 100 kPa35 to 3500 kPa0.7 to 10 Mpa0.7 to 42 MPa
Setting range-100 to 100 kPa-100 to 3500 kPa-0.1 to 10 Mpa-0.1 to 42 MPa
Reference accuracy(Varies by material and measuring span)±0.15%±0.15%±0.15%±0.15%
Fill fluidSilicone oil(for general purpose and high temperature models)Silicone oil (for general purpose, high temperature,high temperature vacuum, and high temperature high vacuum models)Silicone oil(for general purpose models)
Fluorine oil(oxygen and chlorine models)Fluorine oil (oxygen and chlorine models)Fluorine oil(oxygen models)
Waterproof and dust-proof constructionIEC IP66/IP67
Explosion-proof constructionTIIS explosion proof (Exd IICT4)
Range of operating temperatures for liquid part(Varies with pressure)Silicone oil: -40 to 280 °C (varies with fill fluid)Silicone oil:-40 to 180 °C
Fluorine oil: -10 to 120 °CFluorine oil: -10 to 120 °C
Range of operating pressures for liquid part(Varies with temperature)Silicone oil General purpose and high temperature models: from 2 kPa abs 2 kPa abs~Silicone oil General purpose and high temperature models: from 2 kPa abs
High temperature vacuum and high temperature high vacuum models: 0.13 kPa abs
Silicone oil: from 2 kPa abs
Fluorine oil: from 53 kPa absFluorine oil: from 53 kPa absFluorine oil: from 54 kPa abs
Wetted materialSUS316 (diaphragm SUS316L), Hastelloy C, TantalumSUS316 (diaphragm SUS316L)
Power17.9 to 45 V DC
Output signal4 to 20 mA DC (SFN communication), 4 to 20 mA DC (HART® communication)
Process connectionsFlush type: 80 mmFlush type: 80 mm, 50 mm, 40 mmButton diaphragm type
Protruding type: 100 mmProtruding type: 100 mm, 80 mm, 50 mm2B wafer type
2B wafer type2B wafer type 

Inquiries about field instruments and control valves