This is a microprocessor-based smart transmitter with excellent stability. It can measure the absolute pressure of gases, liquids, steam, etc.
- Safe instrumentation: IEC 61508-compliant and SIL2-certified
- Excellent usability: zero/span adjustment without opening the cover
- Various functions: send alarm information by contact output (optional)
Advanced Transmitter Absolute Pressure Transmitters (Model GTX_ _A) are used to measure the absolute pressure of gases, liquids, and steam, as well as to monitor tank pressure. With their extremely wide measurement range (GTX60A: 35 to 3500 kPa, a rangeability of 1:100), they help to cut costs by reducing the number of spare units required.
| Model | GTX30A | GTX60A |
|---|---|---|
| Measurement span | 4~104 kPa | 35~3500 kPa |
| Setting range | 0~104 kPa abs | 0~3500 kPa abs |
| Reference accuracy(Varies by material and measurement span) | ±0.15% | ±0.15% |
| Fill fluid | Silicone oil (general purpose models), fluorine oil (oxygen and chlorine models) | |
| Waterproof and dust-proof construction | IEC IP66/IP67 | |
| Explosion-proof construction | TIIS flameproof (Exd IICT4) KOSHA flameproof FM explosion proof, intrinsic safe and Nonincendive ATEX/NEPSI/IECEx flameproof, intrinsic safe and Type n | |
| Wetted material | SUS316 (diaphragm SUS316L), Alloy C-276, Tantalum | |
| Power | 17.9~42V DC | |
| Output signal | 4 to 20 mA DC (SFN communication) 4 to 20 mA DC (HART® communication) | |
| Safety certification | Safety Integrity Level (SIL) 2 certification | |