![HIC_HMC](/jp/files/default/2023-03/HIC_HMC_690_380.jpg)
Wetted parts of the body and trim of this control valve are high-performance ceramic for excellent corrosion resistance.
- Many applications for the control of acids, bases, and other corrosive fluids
- Uses a compact, high-output, multi-spring diaphragm motor
Structural drawing | Image
![]() | Image
![]() |
---|---|---|
Valve type | Corrosion-resistant type small size ceramic control valve | Corrosion-/abrasion-resistant type ceramic control valve |
Model No. | HMC_ _ _ | HIC_ _ _ |
Size | 1" | 1" to 3" |
Pressure rating | Max. pressure : 1960kPa | Max. pressure : 1960kPa |
End connection | Wafer | Wafer |
Body material | Body : 99% Alminum ceramic, silicon carbide ceramic Casing : ductile cast iron, stainless steel | Body : 99% Alminum ceramic, silicon carbide ceramic Casing : ductile cast iron, stainless steel |
Trim material | 99% Alminum ceramic, silicon carbide ceramic | 99% Alminum ceramic, silicon carbide ceramic |
Temperature range | 0 to 200°C | 0 to 200°C |
Leakage performance | Less than 2.0% of maximum valve capacity | Less than 1.0 to 1.5% of maximum valve capacity |
Cv range | 1 to 4 | 13 to 120 |
Range ability | 30:1 | 30:1 |
Application | Hard slurry service as flue-gas desulfurization, drainage, dissolving pulp slurry, and alumina refining unit | Hard slurry service as flue-gas desulfurization, drainage, dissolving pulp slurry, and alumina refining unit |
Option | - | - |
Control valve with ceramic flow path