A small and lightweight single-function control valve with specifications and structure limited to the range of JIS10K, making specification selection easy.
- Compact and lightweight control valve with high reliability for process control of JIS10K line
- Compact and lightweight design for installation in equipment
- Electric positioner can be selected
| Structural drawing | Image
|
|---|---|
| Valve type | Single Seated Valves |
| Model No. | ACT_ _ _ |
| Size | 1/2 in. to 3 in. |
| Pressure rating | JIS10K |
| End connection | Flange: RF, FF |
| Body material | SCPH2 SCS13A |
| Trim material | SUS316, SUS316 + CoCr-A hardfacing SUS316 + PTFE with carbon fiber |
| Temperature range | 0 to + 200 °C |
| Leakage performance | Classes IV, VI |
| Cv range | 0.4 to 100 |
| Range ability | 20:1 to 50:1 |
| Application | Dedicated control valve for the JIS10K line of chemical, food, textile, machinery equipment markets |
| Option | - |
A wide range of available materials
Products can be provided to meet a variety of body material specifications, such as: carbon steel, which is generally used with water, steam, and fuel oil; highly corrosion resistant stainless steel, which is essential for controlling corrosive fluids; and resin.
Excellent seat leakage performance
Metal seat tight shutoff (class IV) and soft seat tight shutoff (class VI) are available.
High control performance
High control performance is achieved by a combination of wide rangeability and a smart valve positioner.