Electric Valves

Electric top guided single seated control valve Model AGVB_ _ _ / AGVM_ _ _

Model No.
AGVB_ _ _ /AGVM_ _ _
AGVB-e_690_380.jpg

Electric control valve with large capacity, high rangeability, and accurate flow rate characteristics.

  • Compact electrical actuator with either proportional or on-off control
  • Highly reliable control
  • Widely applications for process control where flow shutoff performance is important
Structural drawing
Image
AGVB_AGVM
Valve typeElectric top guided single seated control valve
Model No.AGVB_ _ _ /AGVM_ _ _
Size1/2" to 2"
Pressure ratingmodel AGVB_ _ _ : ANSI/JPI 150, JIS10K
model AGVM_ _ _ : ANSI/JPI 300, JIS16K to 30K
End connectionFlanged : RF, FF
Welded : SW, BW
Body materialCarbon steel
Stainless steel
Trim material440CSS
316SS, 316SS with CoCr-A
316LSS, 316LSS with CoCr-A
Temperature range-196 to 400°C
Leakage performanceClass IV, VI
Cv range0.1 to 50
Range ability20:1 to 50:1 (option 75:1)
Applicationflow control of saturated vapor,
cold and hot water, etc.
Option-

Various body material specifications available

Valves have bodies made of carbon steel for general-use applications like controlling water, steam, and fuel oil, etc., or made of highly corrosion-resistant stainless steel, resin material, etc., as needed for corrosive fluids.

No instrumentation equipment air source required

Valves are suitable for use in various types of equipment without an instrumentation equipment air facility or air conditioning.

Drip-proof structure

The drip-proof structure is equivalent to NEMA4X, IP65.

Motor protection mechanism

Valves are equipped with a thermal protector to prevent motor burnout.

Operational status monitoring

Feedback is available via 4-20 mA analog standard signal, contact signal, and resistance output.

Excellent seat leakage performance

Soft seat tight shutoff (ANSI class VI) is available.

High controllability

The valves offer wide rangeability.

Inquiries about field instruments and control valves