Single Seated Valves

Model ACT_ _ _ pneumatic single-seated control valve specified for JIS10K

Model No.
ACT_ _ _
ACT

A small and lightweight single-function control valve with specifications and structure limited to the range of JIS10K, making specification selection easy.

  • Compact and lightweight control valve with high reliability for process control of JIS10K line
  • Compact and lightweight design for installation in equipment
  • Electric positioner can be selected
Structural drawing
Image
ACT
Valve typeSingle Seated Valves
Model No.ACT_ _ _
Size1/2 in.  to 3 in.
Pressure ratingJIS10K
End connectionFlange: RF, FF
Body materialSCPH2
SCS13A
Trim materialSUS316, SUS316 + CoCr-A hardfacing
SUS316 + PTFE with carbon fiber
Temperature range0 to + 200 °C
Leakage performanceClasses IV, VI
Cv range0.4 to 100
Range ability20:1 to 50:1
ApplicationDedicated control valve for the JIS10K line of chemical, food, textile, machinery equipment markets
Option-

A wide range of available materials

Products can be provided to meet a variety of body material specifications, such as: carbon steel, which is generally used with water, steam, and fuel oil; highly corrosion resistant stainless steel, which is essential for controlling corrosive fluids; and resin.

Excellent seat leakage performance

Metal seat tight shutoff (class IV) and soft seat tight shutoff (class VI) are available.

High control performance

High control performance is achieved by a combination of wide rangeability and a smart valve positioner.