流體名稱
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 氯酸鈉 soldium chlorate | NaClO2 | 10 | ◎ | ◎ | △ 25℃ | ◎ | × | ◎ | ◎ | ||||
| 氯酸鈉 soldium chlorate | NaClO2 | 30 | ◎ | ◎ | △ 25℃ | ◎ | × | ◎ | ◎ | ||||
| 氯酸鈉 soldium chlorate | NaClO2 | 40 | ◎ | ◎ | △ 25℃ | × | × | ◎ | ◎ | ||||
| 硝酸鈉 sodium nitrate | NaNO2 | 60 | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ||||
| 亞砷酸 arsenic, acid, arsenic | HAS2O3 | 10 | ◎ | ◎ | △ | △ | ◎ | ◎ | |||||
| 亞硫酸 sulfurous acid | H2SO3 | 10 | ○ 35℃ | ◎ | ◎ | × | ○ 30℃ | △ | ◎ | ◎ | |||
| 亞硫酸 鈉 sodium sulfite | Na2SO3 | 30 | ◎ | ◎ | ○75℃ △100℃ | ◎ | △ | ◎ | ◎ | ||||
| 氨水 aqueous ammonia | NH4OH | 28 | ○ 35℃ | ○ 45℃ | ○ 65℃ | ○25℃ △ | ○ 80℃ | ○25℃ △ | ◎ | × | △ | ||
| Aquarius (運動飲料) | ◎ | △ | ◎ | ◎ | ◎ | ||||||||
| 飲用水 | H2O | ○ 50℃ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |
| 氯化鋅 zinc chloride | ZnCl2 | 20 | ◎ | ◎ | × | ◎ | ◎ | △ | ◎ | ||||
| 氯化鋅 zinc chloride | ZnCl2 | 50 | ◎ | ◎ | × | ◎ | ◎ | × | ◎ | ||||
| 氯化鋁 aluminum chloride | AlCl3 | 20 | ◎ | ◎ | × | × | ◎ | ◎ | ◎ | × | ◎ | ||
| 氯化氨 ammonium chloride | NH4Cl | 25 | ○ 50℃ | ◎ | ◎ | × | ◎ | ◎ | ◎ | ◎ | △ | ◎ | |
| 氯化氨 ammonium chloride | NH4Cl | 40 | ○ 50℃ | ◎ | ◎ | × | ◎ | × | ◎ | ◎ | △ | ◎ | |
| 氯化鎘 cadmium chloride | CdCl2 | 10 | ◎ | ◎ | △ | △ 75℃ | △ 75℃ | ◎ | |||||
| 氯化鎘 cadmium chloride | CdCl2 | 30 | ◎ | ◎ | △ | △ 25℃ | △ 25℃ | ◎ | |||||
| 氯化鉀 potassium chloride | KCl | 10 | ○ 50℃ | ◎ | ◎ | × | ◎ | ○25℃ △ | ○25℃ △ | ◎ | △ | ◎ | |
| 氯化鉀 potassium chloride | KCl | 40 | ○ 50℃ | ◎ | ◎ | × | ◎ | △ | △ | ◎ | △ 30% | ○ 30% | |
| 氯化鈣 calcium chloride | CaCl2 | 70 | ○ 50℃ | ◎ | ◎ | × | ◎ | × | ◎ | ◎ | ○ 40% | ○ 60℃, 50% | |
| 氯化亞錫 tin chloride | SnCl2 | 10 | ◎ | ◎ | × | × | ◎ | ◎ | |||||
| 氯化亞錫 tin chloride | SnCl2 | 30 | ◎ | × | × | × | ◎ | ◎ | |||||
| 氯化亞鐵 ferrous chloride | FeCl2 | 50 | ○ 50℃ | ◎ | ◎ | × | ◎ | △ | ◎ | ◎ | × | × | |
| 氯化亞銅 copper chloride | CuCl | 40 | ◎ | × | △ | △ 50℃ | ◎ | × | |||||
| 氯化汞 bichloride of mercury | HgCl2 | 40 | ◎ | ◎ | × | ◎ | △ 75℃ | ◎ | ◎ | ||||
| 氯化錫 tin chloride | SnCl4 | 20 | ◎ | × | △ | △ | ◎ | ◎ | |||||
| 氯化錫 tin chloride | SnCl4 | 50 | ◎ | × | × | △ | ◎ | ◎ | |||||
| 氯化鐵 ferric chloride | FeCl3 | 10 | ◎ | ◎ | × | ◎ | ○ 50℃ | ◎ | ○ 25℃ | × | ◎ | ||
| 氯化鐵 ferric chloride | FeCl3 | 30 | ◎ | ◎ | × | ◎ | △ | ◎ | ○ 25℃ | ◎ | |||
| 氯化鐵 ferric chloride | FeCl3 | 50 | ◎ | ◎ | × | ◎ | × | ◎ | ○ 25℃ | ◎ | |||
| 氯化銅 copper chloride | CuCl2 | 40 | ○ 50℃ | ◎ | × | △ | △ 25℃ | ◎ | × | ||||
| 氯化鈉 sodium chloride | NaCl | 25 | ○ 50℃ | ◎ | ◎ | × | ◎ | × | ◎ | ◎ | × | ◎ | |
| 氯化鎳 nickel chloride | NiCl2 | 20 | ◎ | ◎ | × | ◎ | ◎ | ◎ | ○ 100% | ○ 100% | |||
| 氯化鋇 barium chloride | BaCl2 | 25 | ○ 50℃ | ◎ | ◎ | × | ○ 50℃,20% | △ | ◎ | ◎ | △ | ○ 20% | |
| 氯化鎂 magnesium chloride | MgCl2 | 40 | ○ 50℃ | ◎ | × | ◎ | ◎ | ◎ | ◎ | ||||
| 氯化鋰 lithium chloride | LiCl | 60 | ○ 52℃ | ◎ | × | ◎ | ◎ | ◎ | ◎ | ||||
| 鹽酸 hydro- chloric acid | HCl | 10 | ◎ | ◎ | × | ○ 25℃ | ○ 25℃ | ○ ※1 | ○ 30℃ | × | ◎ | ||
| 鹽酸 hydro- chloric acid | HCl | 35 | ○ 70℃ | ◎ | × | × | △ 25℃ | ○ ※1 | ○ 30℃ | × | ○ 30% | ||
| 氯酸钙 calcium chlorate | Ca(Col3)2 | 30 | ◎ | △ 1% | ○ 25℃ | △ | ◎ | ◎ | |||||
| 氯酸鈉 sodium chlorate | NaClO3 | 40 | ◎ | ◎ | × | ○ 25℃ | △ | ◎ | ◎ | ||||
| 亞鐵氰化鉀 yellow prussiate, potassium ferrocyanide | K4[Fe(CN)6] | 30 | ◎ | ◎ | △ | ◎ | △ | ◎ | ◎ | ◎ | |||
| 王 水 nitrohydro- chloric acid | 1HNO3+3HC | × | ◎ | ◎ | × | ○ 25℃ | × | ◎ | × | × | × | ||
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 海 水 sea water | ○ 50℃ | ◎ | ◎ | × | ◎ | △ | ◎ | ◎ | × | ||||
| 高氯酸 perchloric acid | HClO4 | 70 | ○ 40℃ | ◎ | × | ◎ | ◎ | × | |||||
| 過氧化氫 hydrogen peroxide | H2O2 | 30 | × | ○ 45℃ | ○ 65℃ | ◎ | × | ○ 25℃ | ◎ | × | △ 60℃, 20% | ◎ | |
| 苛性鈉 custic soda,sodium hydroxide | NaOH | 40 | ○ 35℃ | ◎ | ◎ | ※2 ○ | ◎ | △ | × | ◎ | ◎ | △ | |
| 苛性鈉 custic soda,sodium hydroxide | NaOH | 50 | ○ 35℃ | ◎ | ◎ | ○ 80℃ | △ | △ | × | ◎ | ◎ | △ | |
| 高锰酸鉀 potassium permanganate | KMnO4 | 30 | × | ○ 80℃ | ○ 90℃ | △ | △ | ◎ | ◎ | ||||
| 過硫酸氨 ammonium persulfate | (NH4)2S2O8 | 30 | × | ◎ | ◎ | ○50℃ △ | × | ◎ | ◎ | ||||
| 過硫酸氨 ammonium persulfate | (NH4)2S2O8 | 50 | × | ◎ | ◎ | ○ 50℃ | × | ◎ | ◎ | ||||
| 過硫酸鉀 potassium persulfate | K2S2O8 | 10 | ◎ | ◎ | ◎ | ○ 75℃ | ○ 50℃ | ◎ | ◎ | ||||
| 甲酸 formic acid | CH2O2 | 10 | × | ◎ | ◎ | × | × | ○50℃ △ | ◎ | ◎ | △ | ◎ | |
| 甲酸 formic acid | CH2O2 | 50 | × | ◎ | ◎ | × | × | ○50℃ △ | ◎ | ◎ | △ | ◎ | |
| 牛奶 milk | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |||||||
| 檸檬酸 citric acid | ○ 50℃ | ◎ | ◎ | ||||||||||
| 鉻酸 chromic acid | H2CrO4 | 50 | △ | ◎ | × | ◎ | △ | ○ ※1 | ◎ | × | ○ 30% | ||
| 鉻酸鈉 sodium chromate | Na2CrO4 | 60 | △ | ◎ | ◎ | ◎ | ◎ | ○ ※1 | ◎ | ◎ | ◎ | ||
| 氯乙酸 chloroacetic acid | C2H3ClO2 | 60 | ◎ | ◎ | × | △ | △ | ◎ | ◎ | ||||
| 氯磺酸 chloro- sulfonic acid | HSO3l | 10 | × | ○ 20℃ | ○ 90℃ | × | × | △ 25℃ | ◎ | ◎ | |||
| 氯磺酸 chloro- sulfonic acid | HSO3l | 45 | × | ○ 80℃ | ○ 90℃ | × | × | ○ 25℃ | ◎ | ◎ | |||
| 矽酸鈉 sodium silicate | Na2SiO3 | 10 | ◎ | ◎ | ◎ | ◎ | △ | ◎ | ◎ | ||||
| 矽氫氟酸 hydrofluosi- licic acid | H2SiF6 | 35 | ◎ | ◎ | × | × | × | × | ◎ | ||||
| 五氯化銻 antimony penta chlorate | SbCl5 | 50 | ◎ | ◎ | × | × | ◎ | ◎ | |||||
| 咖啡 caffe | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |||||||
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 醋酸 acetic acid | C2H4O2 | 40 | × | ◎ | ◎ | ◎ | ◎ | ○ ※2 | ◎ | ◎ | × | ◎ | |
| 醋酸 acetic acid | C2H4O2 | 75 | × | ◎ | ◎ | △ | ◎ | ○ ※2 | ◎ | ◎ | × | ◎ | |
| 醋酸鈉 sodium acetate | NaCH3CO2 | 100 | × | ◎ | ◎ | ○ 10% | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |
| 醋酸鉛 lead acetate | Pb(CH3CO2)2 | 40 | × | ◎ | ◎ | △ | ○ 25℃ | × | ◎ | × | |||
| 三氯化銻 antimony trichlorate | SbCl3 | 10 | ◎ | ◎ | × | × | ◎ | × | |||||
| 次氯酸 hypochlorous acid | HClO | 20 | ◎ | ◎ | × | × | ◎ | ◎ | × | ||||
| 次氯酸鈣 calcium hypochlorite | Ca(ClO)2 | 20 | ○ 90℃ | ◎ | × | ◎ | △ | ◎ | ◎ | × | ◎ | ||
| 次氯酸鈉 (漂白水) sodium hypochlorite | NaOCl | 15 | × | ○ 70℃ | ◎ | × | ◎ | ◎ | ◎ | ◎ | × | ○ 10℃ | |
| 次氯酸鈉 (漂白水) sodium hypochlorite | NaOCl | 20 | × | ○ 90℃ | × | ◎ | ○ 50℃ | ◎ | ◎ | × | |||
| 氰化銅 copper cyanide | Cu(CN)2 | 10 | ○ 50℃ | ◎ | ◎ | ◎ | △ | ◎ | ◎ | ||||
| 氰化鈉 sodium cyanide | NaCN | 10 | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | △ 40℃ | ◎ | |||
| 氰化鈉 sodium cyanide | NaCN | 20 | ◎ | ◎ | × | ◎ | ◎ | ◎ | ◎ | ||||
| 氫氰酸 hydrocyanic | CHN | ◎ | ○ 93℃ | × | × | × | ○ 93℃ | ○ | |||||
| 重亞硫酸氫鈉 heavy sodium bisulfite | NaHSO3 | 40 | ◎ | ◎ | × | △ | △ | ◎ | ◎ | ||||
| 氫溴酸 hydracid bromide | HBr | 48 | × | ○ 70℃ | ◎ | × | ◎ | × | ◎ | ◎ | |||
| 溴化鈉 sodium bromide | NaBr | 50 | ◎ | ◎ | △ | × | △ | ◎ | ◎ | △ | |||
| 溴化鋰 lithium bromide | LiBr | 60 | ◎ | × | ◎ | ◎ | |||||||
| 草酸 oxalic acid | C2H2O42H2O | 45 | ◎ | ◎ | × | × | △ | ◎ | ◎ | × | |||
| 重碳酸氨 heavy ammonium carbonate | NH4HCO3 | 50 | ◎ | ◎ | ◎ | △ | ◎ | ◎ | |||||
| 重碳酸鉀 heavy potassium carbonate | KHCO3 | 30 | ◎ | ◎ | ◎ | ◎ | △ | ◎ | ◎ | ||||
| 重碳酸鉀 heavy potassium carbonate | 50 | ◎ | ◎ | △ | ◎ | △ | ◎ | ◎ | |||||
| 重碳酸鈉 heavy sodium carbonate | NaHCO3 | 20 | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ||
| 重氟化銨 heavy ammonium fluoride | NH4HF2 | 5 | ◎ | ◎ | × | × | △ | × | ◎ | ||||
| 重硫化鈉 heavy sodium sulfide | NaHS | 40 | ◎ | ◎ | ◎ | ◎ | ◎ | ||||||
| 重硫化鈉 heavy sodium sulfite | NaHSO4 | 20 | ◎ | ◎ | × | ○ 25℃ | △ 50℃ | ◎ | ◎ | ||||
| 硝酸 hitric acid | HNO3 | 10 | × | ○ 50℃ | ◎ | ◎ | ◎ | ○ 50℃ | ○ ※1 | ◎ | × | ||
| 硝酸 hitric acid | HNO3 | 40 | × | ◎ | ○ 25℃ | ◎ | ○ 50℃ | ○ ※1 | ◎ | × | |||
| 硝酸 hitric acid | HNO3 | 70 | × | ○ 90℃ | × | △ | × | ○ ※1 | ◎ | × | |||
| 硝酸鋁 alminum nitrate | Al(NO3)3 | 10 | ◎ | ◎ | ○ 75℃ | ◎ | △ 25℃ | ○ ※1 | ◎ | ||||
| 硝酸銨 ammonium nitrate | NH4NO3 | 40 | × | ◎ | ◎ | ◎ | × | △ | ◎ | ◎ | ◎ | ||
| 硝酸鉀 potassium nitrate | KNO3 | 40 | ○ 50℃ | ◎ | ◎ | △ | ◎ | △ | ◎ | ◎ | △ | ||
| 硝酸鈣 calcium nitrate | Ca(NO3)2 | 10 | ○ | ◎ | ◎ | △ | ◎ | △ | ◎ | ◎ | △ | ||
| 硝酸銀 silver nitrate | AgNO3 | 20 | ○ 50℃ | ◎ | ◎ | ○25℃ △ | ○ 50℃ | ○ 25℃ | ◎ | ◎ | × | ||
| 硝酸銀 silver nitrate | AgNO3 | 50 | ○ 50℃ | ◎ | ◎ | ○25℃ △ | ○ 25℃ | ◎ | ◎ | × | |||
| 硝酸鐵 ferric nitrate | Fe(NO3)3 | 10 | ◎ | ◎ | △ | ○ 25℃ | ◎ | ◎ | |||||
| 硝酸鐵 ferric nitrate | Fe(NO3)3 | 50 | ◎ | ◎ | △ | △ 25℃ | ◎ | ◎ | |||||
| 硝酸銅 copper nitrate | Cu(NO3)2 | 10 | ◎ | ◎ | ◎ | ○ 25℃ | △ 25℃ | ◎ | ◎ | ||||
| 硝酸銅 copper nitrate | Cu(NO3)2 | 50 | ◎ | ◎ | △ | ○ 25℃ | △ 25℃ | ◎ | ◎ | ||||
| 硝酸鈉 sodium nitrate | NaNO3 | 30 | ◎ | ◎ | × | ◎ | ○ 25℃ | ◎ | ◎ | ◎ | |||
| 硝酸鈉 sodium nitrate | NaNO3 | 50 | ◎ | ◎ | × | ◎ | × | ◎ | ◎ | ◎ | |||
| 硝酸鎳 nickel nitrate | Ni(NO3)2 | 10 | ◎ | ◎ | △ | △ 25℃ | ◎ | ◎ | × | ||||
| 硝酸鎳 nickel nitrate | Ni(NO3)2 | 50 | ◎ | ◎ | △ 25℃ | × | ◎ | ◎ | × | ||||
| 硝酸鎂 magnesium nitrate | Mg(NO3)2 | 10 | ◎ | ◎ | △ | △ | △ | ◎ | ◎ | ||||
| 兌水的燒酒 | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |||||||
| 醬油 soy sauce | ◎ | ◎ | × | ◎ | × | ◎ | ◎ | ||||||
| 氫氧化鋁 alminum hydroxide | Al(OH)3 | 10 | ◎ | ◎ | △ | ◎ | △ | ◎ | ◎ | ◎ | ◎ | ||
| 氫氧化銨 ammonium hydroxide | NH4OH | 30 | ○ 50℃ | ○ 90℃ | ◎ | ○25℃ △ | ◎ | ○25℃ △ | × | ◎ | × | △ 30% | |
| 氫氧化鉀 pottasium hydroxide | KOH | 10 | ○ 35℃ | ○ 80℃ | ○ 90℃ | × | ◎ | △ | ◎ | ◎ | ◎ | ◎ | |
| 氫氧化鉀 pottasium hydroxide | KOH | 45 | ○ 35℃ | ○ 90℃ | × | × | △ | × | ◎ | ◎ | ◎ | ||
| 氫氧化鈣 calcium hydroxide | Ca(OH)2 | 50 | ○ 50℃ | ◎ | △ | ◎ | △ | ◎ | ◎ | △ 10%, 100% | ○ 20% | ||
| 氫氧化鈉 sodium hydroxide | NaOH | 40 | ○ 35℃ | ◎ | ◎ | ○ ※1 | ◎ ※1 | △ | × | ◎ | ◎ | △ | |
| 氫氧化鈉 sodium hydroxide | NaOH | 50 | ○ 35℃ | ◎ | ◎ | ○ 80℃ | △ | △ | × | ◎ | ◎ | △ | |
| 氫氧化鋇 barium hydroxide | Ba(OH)2 | 30 | ○ 50℃ | ◎ | ◎ | △ | ◎ | △ | × | ◎ | ◎ | ||
| 氫氧化鎂 magnesium hydroxide | Mg(OH)2 | 10 | ○ | ◎ | ◎ | △ | △ 25℃ | × | ◎ | ||||
| 石碳酸 carbolic acid | C6H6O | 10 | ◎ | ◎ | △ | ◎ | ◎ | ◎ | |||||
| 赤血鹽 potassium ferricyanide, red prussiate of potash | K3[Fe(CN)6] | 30 | ◎ | ◎ | △ | ◎ | △ | ◎ | × | ||||
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 碳酸銨 ammonium carbonate | (NH4)2CO3・H2O | 50 | ◎ | ◎ | △ | △ | ◎ | ◎ | |||||
| 碳酸鉀 potassium carbonate | K2CO3 | 20 | ◎ | ◎ | △ | ◎ | △ | × | ◎ | △ | |||
| 碳酸鉀 potassium carbonate | K2CO3 | 60 | ◎ | ◎ | △ | △ | △ | × | ◎ | △ | |||
| 碳酸鈣 calcium carbonate | CaCO3 | 10 | ◎ | ◎ | × | ◎ | × | ◎ | ◎ | △ | |||
| 碳酸鈉 sodium carbonate | Na2CO3 | 10 | ◎ | ◎ | × | ◎ | ◎ | ◎ | ◎ | ◎ | |||
| 碳酸鈉 sodium carbonate | Na2CO3 | 30 | ◎ | ◎ | × | ◎ | △ | ◎ | ◎ | ◎ | |||
| 碳酸鋇 barium carbonate | BaCO3 | 10 | ◎ | ◎ | △ | ○ 25℃ | × | ◎ | ◎ | ||||
| 碳酸鎂 magnesium carbonate | MgCO3 | 10 | ◎ | ◎ | △ | △ | △ | ◎ | ◎ | ||||
| 硫代硫酸鈉 sodium thiosulfate | Na2S2O3 | 60 | ○ 50℃ | ◎ | ◎ | ◎ | △ | ◎ | ◎ | ||||
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 二氧化氯 chlorine dioxide | ClO2 | 15 | ◎ | ◎ | × | ◎ | △ | ◎ | ◎ | ||||
| 日本酒 | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |||||||
| 日本茶 (綠茶) green tea | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |||||||
| 尿酸 uric acid | CH4N2O | 50 | ◎ | △ | ○ ※2 | ◎ | ◎ | ||||||
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 砷酸 arsenic acid | H3AsO4 | 10 | ◎ | ◎ | △ | △ | ◎ | ◎ | △ | ||||
| 砷酸 arsenic acid | H3AsO4 | 30 | ◎ | ◎ | △ | × | ◎ | ◎ | |||||
| 亞硫酸氫鈉 sodium hydrosulfite | NaHS | 10 | ◎ | ◎ | ◎ | ○ 25℃ | ◎ | ◎ | |||||
| 啤酒 beer | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |||||||
| 苯酚 phenol | C6H6O | 10 | ◎ | ◎ | △ | ◎ | ◎ | ◎ | |||||
| 鐵氰化鉀 (赤血鹽) | K3[Fe(CN)6] | 30 | ◎ | △ | ◎ | △ | ◎ | × | △ | ||||
| 鐵氫化鈉 sodium ferricyanide | Na3[Fe(CN)6] | 10 | ◎ | △ 50℃ | △ 25℃ | ◎ | × | ||||||
| 亞鐵氫化鉀 (黃血鹽) potassium ferrocyanide | K4[Fe(CN)6] | 30 | ◎ | △ | ◎ | △ | ◎ | × | |||||
| 亞鐵氫化鈉 sodium ferrocyanide | Na[Fe(CN)6] | 10 | △ | △ | ◎ | × | |||||||
| 氟化鋁 alminum fluoride | AlF3 | 20 | ◎ | × | × | △ 25℃ | ◎ | × | △ | ||||
| 氟化銨 ammonium fluoride | NH4F | 10 | ◎ | △ 25℃ | ○ 30℃ | ◎ | ◎ | × | × | ||||
| 氟化銨 ammonium fluoride | NH4F | 40 | ◎ | × | × | ◎ | ◎ | × | △ 20% | ||||
| 氟矽酸 fluosilicate | H2SiF6 | 10 | ○ 90℃ | × | × | × | ◎ | × | |||||
| 氫氟酸 fluoric acid | HF | 20 | × | ◎ | × | × | × | △ | ◎ | × | × | ||
| 氟硼酸 | HBF4 | 20 | × | × | × | ◎ | × | ||||||
| 硼酸 boracic acid | H3BO4 | 50 | ○ 90℃ | ◎ | × | ◎ | ◎ | ◎ | ◎ | △ 20% | |||
| 寶礦力水得(運動飲料) | ◎ | △ | ◎ | ◎ | ◎ | ||||||||
| 甲醛 (福馬林) formaldehyde | CH2O | 40 | ◎ | ◎ | ◎ | ◎ | △ | ◎ | ◎ | ||||
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 硫酸鉻鉀 chrome alum | KAl(SO4)2・12H2O | 10 | △ | △ | ◎ | ◎ | |||||||
| 水(飲用水) | H2O | ○ 50℃ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ||||
| 水(海水) | ○ 50℃ | ◎ | × | ◎ | △ | ◎ | ◎ | × | |||||
| 水(汙水) | ○ 50℃ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |||||
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 碘溶液 iodine | I | 10 | ◎ | × | × | △ | ◎ | ◎ | |||||
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 硫化銨 ammonium sulfide | (NH4)2S | 40 | ◎ | △ | △ | ◎ | ◎ | ||||||
| 硫化氫 hydrogen sulfide | H2S | 10 | ◎ | ◎ | × | × | ◎ | ◎ | |||||
| 硫化鈉 sodium sulfide | Na2S | 10 | ◎ | ◎ | ○75℃ △ | ◎ | △ | ◎ | ◎ | ||||
| 硫化鈉 sodium sulfide | Na2S | 50 | ◎ | ◎ | × | × | △ | ◎ | ◎ | ||||
| 硫化鋇 barium sulfide | BaS | 10 | ◎ | ◎ | △ 25℃ | ○ 25℃ | × | ○ 50℃ | ○ 50℃ | ○ 10℃ | |||
| 硫酸 sulfuric acid | H2SO4 | 50 | ○ 35℃ | ◎ | ◎ | × | × | × | △ | ◎ | △ 10℃, 40% | △ | |
| 硫酸 sulfuric acid | H2SO4 | 80 | × | ◎ | ◎ | × | × | × | △ | ◎ | × | △ 70% | |
| 硫酸 sulfuric acid | H2SO4 | 96 | × | ◎ | ◎ | × | × | × | △ | ◎ | × | × | |
| 硫酸鋅 zinc sulfate | ZnSO4 | 40 | ◎ | ◎ | × | ◎ | △ | ◎ | ◎ | ||||
| 硫酸鋁 alminum sulfate | Al2(SO4)3・18H2O | 50 | ○ 50℃ | ○ 50℃ | ◎ | × | ◎ | ◎ | ◎ | ◎ | |||
| 硫酸鋁 鉀 | KAl(SO4)3・18H2O | 10 | ◎ | △ | △ | ◎ | ◎ | ||||||
| 硫酸銨 ammonium sulfate | (NH4)2SO4 | 20 | ○ 50℃ | ◎ | ◎ | △ | ◎ | △ | ◎ | ◎ | △ | ||
| 硫酸銨 ammonium sulfate | (NH4)2SO4 | 40 | ○ | ◎ | ◎ | △ | × | △ | ◎ | ◎ | △ | ||
| 硫酸鉀 potassium sulfate | K2SO4 | 20 | ○ 50℃ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | △ | ◎ | |
| 硫酸鈣 calcium sulfate | Ca(SO4) | 10 | ○ 50℃ | ◎ | ◎ | ◎ | ○ 50℃ | × | ◎ | ◎ | |||
| 硫酸鉻 chrome sulfate | CrSO4 | 20 | × | ◎ | × | △ | ◎ | ◎ | |||||
| 硫酸亞鐵 ferrous sulfate | FeSO4 | 50 | ◎ | ◎ | × | ◎ | △ | ◎ | ◎ | ||||
| 硫酸鐵 ferric sulfate | Fe2(SO4)3 | 10 | ◎ | ◎ | ◎ | ○ 25℃ | ○50℃ △75℃ | ◎ | ◎ | × | ◎ | ||
| 硫酸鐵 ferric sulfate | Fe2(SO4)3 | 30 | ◎ | ◎ | × | ○ 25℃ | ○50℃ △75℃ | ◎ | ◎ | ◎ | |||
| 硫酸銅 copper sulfate | CuSO4 | 30 | ◎ | ◎ | × | △ | ◎ | ◎ | ○ 50℃ | △ 10℃ | |||
| 硫酸鈉 sodium sulfate | Na2SO4 | 10 | ○ 50℃ | ◎ | ◎ | ◎ | △ | △ | ◎ | ◎ | △ | ◎ | |
| 硫酸鈉 sodium sulfate | Na2SO4 | 30 | ○ 50℃ | ◎ | ◎ | △ | △ | △ | ◎ | ◎ | △ | ◎ | |
| 硫酸鎳 nickel sulfate | NiSO4 | 10 | ○ 50℃ | ◎ | ◎ | △ | △ | ◎ | ◎ | ◎ 100% | ◎ 100% | ||
| 硫酸鋇 barium sulfate | BaSO4 | 10 | ○ 50℃ | ◎ | ◎ | △ | × | ◎ | ◎ | △ 100% | |||
| 硫酸鎂 magnesium sulfate | MgSO4 | 40 | ◎ | ◎ | ◎ | ◎ | × | ◎ | ◎ | △ 30% | |||
| 磷酸 phosphoric acid | H3PO4 | 50 | ○ 50℃ | ◎ | ◎ | × | × | × | ○ ※3 | ◎ | × | △ | |
| 磷酸 phosphoric acid | H3PO4 | 85 | ○ 50℃ | ◎ | ◎ | × | × | × | ○ ※3 | ◎ | × | × | |
| 磷酸銨 ammonium phosphate | (NH4)3PO4 | 10 | ◎ | ◎ | × | ◎ | × | ◎ | ◎ | △ | ◎ | ||
| 磷酸氫鈉 sodium phosphate | Na2HPO4 | 50 | ◎ | ◎ | × | ◎ | ◎ | △ 25℃ | ◎ | ||||
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 紅酒 wine | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |||||||
| 內襯 | 電極 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 流體名稱 | 化學式 | 濃度% | 聚氨酯橡 膠 | ETFE | PFA | SUS316L | 鈦 | 哈氏合金 C-276 | 鉭 | 白金 | 碳化钨 | 鎳 | 鋯 |
| 紅酒 wine | ◎ | ◎ | ◎ | ◎ | ◎ | ◎ | |||||||