Differential Pressure Transmitter / Pressure Transmitters Advanced Transmitter Model JT_9_ _S/W

Sanitary Differential Pressure / Pressure Transmitters Model JTC9_ _ _/JTE9_ _ _

Model No.
JTC929S, JTC940S, JTE929S, JTE930S
GTX_sanitary

Sanitary Differential Pressure/Pressure Transmitters (Model JTC9_ _ _/JTE9_ _ _) with built-in microprocessors meet sanitary standards while maintaining high reproducibility and precise accuracy. Connection to pipes is by ISO-compliant sanitary-use clamps for easy attachment, removal, and maintenance.

ModelJTC929SJTC940SJTE929SJTE930S
Measurement span2.5 to 100 kPa70 to 3500 kPa2.5 to 100 kPa35 to 700 kPa
Setting range-100 to 100 kPa-100 to 3500 kPa-100 to 100 kPa-100 to 700 kPa
Reference accuracy(Varies by material and measurement span)±0.3%±0.2%±0.3%±0.2%
Fill fluidPropylenglycol (a food additive)
Waterproof and dust-proof constructionIEC IP66/IP67
Explosion-proof constructionTIIS explosion proof (Exd IICT4)
Range of operating temperatures for liquid part(Varies with pressure)-10 to 121°C
Steam wash time: 150 °C for 60 min
Range of operating pressures for liquid part(Varies with temperature)from 10 kPa abs
Wetted materialSUS316 (diaphragm SUS316L)
Power17.9 to 45 V DC
Output signal4 to 20 mA DC (SFN communication)
4 to 20 mA DC (HART® communication)
Process connectionsISO 100 (4S) clampsISO 50 (2S), 80 (3S), 100 (4S) clamp connections
ISO 50 (2S) Domend cap nut

Product inquiry