Model MPC_ _ _ _ mass flow controllers can be mounted in a control panel and provide advanced flow control.
- Small and lightweight
- Easy operation and installation
- Easy setup
- Compact (front panel: 48 × 48 mm, depth: 73.7 mm) and lightweight (300 g)
- Easy operation and easy-to-read digital display
- High-speed control (1 second until the set value is reached)
- Various functions
- Cumulative flow volume
- Flow rate alarm output
- Multi-flow rate setting
- Gas type switching
- Slow start
- Automatic shutoff
- Analog input/output (optional)
- RS-485 communication (optional)
- PC loader, etc.
- Easy installation
Specifications
| Model No. | MPC9500 | MPC0002 | MPC0005 | MPC0020 | |
|---|---|---|---|---|---|
| Valve type | Proportional solenoid valve | ||||
| Valve operation | Normally closed (N. C.) when de-energized | ||||
| Standard full-scale flow rate | 0.500 | 2.00 | 5.00 | 20.0 | |
| (nitrogen equivalent) | L/min(standard) | L/min(standard) | L/min(standard) | L/min(standard) | |
| Applicable gas type | Nitrogen/air, argon, carbon dioxide (CO2) | ||||
| The gas must be dry and not contain corrosive components (chlorine, sulfur, acid, etc.). | |||||
| Also, it must be a clean gas, without dust or oil mist. | |||||
| Pressure | Operating differential pressure range | 0.3 MPa max. | 0.05–0.3 MPa | ||
| Pressure resistance | 0.5 MPa(gauge) | ||||
| Flow rate setting | Method | (1) Front panel keys (2) External voltage input (for models with an analog I/O function only) (3) Loader communication (the MLP200 loader package for the MPC is required) (4) RS-485 communication (for models with the RS-485 communication function only) | |||
| Event output | Number of outputs | 2 | |||
| External contact input | Number of inputs | 2 | |||
| Power | Rated power | 24 V DC, current consumption: 300 mA max. | |||
| Gas-contacting part material | Brass (Ni plated), stainless steel, Teflon, fluoroelastomer | ||||
| Connection method | Rc1/8 | ||||
| Weight | Approx. 300 g | ||||
Inquiries about control products