Mass Flow Controllers

Panel Mount Mass Flow Controller Model MPC_ _ _ _

Model No.
MPC_ _ _ _
MPC

Model MPC_ _ _ _ mass flow controllers can be mounted in a control panel and provide advanced flow control.

  • Small and lightweight
  • Easy operation and installation
  • Easy setup
  • Compact (front panel: 48 × 48 mm, depth: 73.7 mm) and lightweight (300 g)
  • Easy operation and easy-to-read digital display
  • High-speed control (1 second until the set value is reached)
  • Various functions
    • Cumulative flow volume
    • Flow rate alarm output
    • Multi-flow rate setting
    • Gas type switching
    • Slow start
    • Automatic shutoff
    • Analog input/output (optional)
    • RS-485 communication (optional)
    • PC loader, etc.
  • Easy installation

Specifications

Model No.MPC9500MPC0002MPC0005MPC0020
Valve typeProportional solenoid valve
Valve operationNormally closed (N. C.) when de-energized
Standard full-scale flow rate0.5002.005.0020.0
(nitrogen equivalent)L/min(standard)L/min(standard)L/min(standard)L/min(standard)
Applicable gas typeNitrogen/air, argon, carbon dioxide (CO2)
The gas must be dry and not contain corrosive components (chlorine, sulfur, acid, etc.).
Also, it must be a clean gas, without dust or oil mist.
PressureOperating differential pressure range0.3 MPa max.0.05–0.3 MPa
Pressure resistance0.5 MPa(gauge)
Flow rate settingMethod(1) Front panel keys (2) External voltage input (for models with an analog I/O function only)
(3) Loader communication (the MLP200 loader package for the MPC is required) (4) RS-485 communication (for models with the RS-485 communication function only)
Event outputNumber of outputs2
External contact inputNumber of inputs2
PowerRated power24 V DC, current consumption: 300 mA max.
Gas-contacting part materialBrass (Ni plated), stainless steel, Teflon, fluoroelastomer
Connection methodRc1/8
WeightApprox. 300 g