Burner Controller model AUR890 were developed as an upgrade for the model RA890 ProtectoRelay, and are designed for batch operation of combustion equipment (at least one start and stop in a 24-hour period). This device is used in combination with model AUD100 /110/120 Advanced Ultraviolet Flame Detector or a flame rod. For combustion equipment that operates continually for 24 hours or longer, use a burner controller designed for continuous operation instead of this device. This device is structured for external instrumentation of the prepurge function. It automatically ignites the pilot and main burners and monitors the flame. In addition, when flame failure occurs, this device locks out the combustion equipment.
| Model | AUR890G-13_ / AUR890G-23_ / AUR890G-330 / AUR890G-63_ |
|||||
|---|---|---|---|---|---|---|
| Application | Batch-operated combustion systems burning gas, oil, or gas/oil mixture | |||||
| Compatible flame detector | Model AUD100/110/120 ultraviolet sensor | |||||
| Lockout timing | 13.5 ± 1.5 s | |||||
| Main burner combustion standby | 0.4 s | |||||
| Flame failure response timing |
Model AUD100/110/120 ultraviolet sensor: 3 ± 1 s (when flame voltage is 3 V) |
|||||
| Reset timing | 1 s or longer (reset switch or contact reset input) * | |||||
| False flame detection time | 15 s | |||||
| Operation at ignition failure | Lockout | |||||
| Operation at flame failure | Lockout | |||||
| Rated power supply | 100 V AC / 120V AC / 200 V AC / 220 V AC (depending on the model), 50 Hz or 60 Hz | |||||
* If no alarm has occurred, input from the RESET switch and the contact reset terminal is not accepted.
| Model | AUR890F-11_-1 / AUR890F-13_-1 / AUR890F-21_-1 / AUR890F-23_-1 / AUR890F-310-1 / AUR890F-330-1 / AUR890F-61_-1 / AUR890F-63_-1 |
|||||
|---|---|---|---|---|---|---|
| Application | Batch-operated combustion systems burning gas | |||||
| Compatible flame detector | Flame rod | |||||
| Lockout timing | 13.5 ± 1.5 s | |||||
| Main burner combustion standby | 0.4 s | |||||
| Flame failure response timing | Flame rod (Ionization): 1 s max (when flame voltage is 2 V) | |||||
| Reset timing | 1 s or longer (reset switch or contact reset input) * | |||||
| False flame detection time | 15 s | |||||
| Operation at ignition failure | Lockout | |||||
| Operation at flame failure | Lockout | |||||
| Rated power supply | 100 V AC /120 V AC / 200 V AC / 220 V AC (depending on the model), 50 Hz or 60 Hz | |||||
* If no alarm has occurred, input from the RESET switch and the contact reset terminal is not accepted.
For more details, refer to Model AUR890 manual.
Model AUR890 manual
Download the replacement guide for model RA890 (included with purchase).
Azbil corporation has over 110 years of experience as a specialized manufacturer of measurement and control automation, and more than 60 years of experience in the flame safeguard equipment business, with installations worldwide. We are proud to provide the burner controller model AUR890 as the replacement for the model RA890. Please feel free to contact us.